SGENTX – Synchronous generator model

Block SymbolLicensing group: MODEL
Qt SVG Document Exported by REXYGEN Studio uf pm pl ql um fm MODE R1 if u1 u i p q freq phir phiu phim cos E SGENTX

Function Description
The function block description is not yet available. Below you can find partial description of the inputs, outputs and parameters of the block. Complete documentation will be available in future revisions.

This block does not propagate the signal quality. More information can be found in the 1.4 section.

Input

uf

Feed voltage [p.u.]

Double (F64)

pm

Prime mover torque [p.u.]

Double (F64)

pload

Load active power [p.u.]

Double (F64)

qload

Load reactive power [p.u]

Double (F64)

MODE

1=grid operation, 0=island operation

Bool

R1

Model state reset

Bool

Parameter

um

Mains voltage [p.u.]  0.011

Double (F64)

fm

Mains frequency [p.u.]  0.011

Double (F64)

pn

Nominal power [VA]  10000000.0

Double(F64)

un

Nominal RMS voltage [V]  6000.0

Double (F64)

fn

Nominal frequency [Hz]  1.0

Double (F64)

pp

Number of pole pairs   1  1000 2

Long (I32)

ZM

on=constant impedance mode, off=constant power mode

Bool

J

Mass of inertia [p.u.]  0.0006

Double (F64)

Tdoi

D-axis transient time constant (open winding) [p.u.]  0.0354

Double (F64)

Tdoii

D-axis subtransient time constant (open winding) [p.u.]  0.0354

Double (F64)

Tqoi

Q-axis transient time constant (open winding) [p.u.]  0.0354

Double (F64)

Tqoii

Q-axis subtransient time constant (open winding) [p.u.]  0.0354

Double (F64)

Xd

D-axis static impedance [p.u.]  0.0428

Double (F64)

Xdi

D-axis transient impedance [p.u.]  0.0428

Double (F64)

Xdii

D-axis subtransient impedance [p.u.]  0.0428

Double (F64)

Xq

Q-axis static impedance [p.u.]  0.0428

Double (F64)

Xqi

Q-axis transient impedance [p.u.]  0.0428

Double (F64)

Xqii

Q-axis subtransient impedance [p.u.]  0.0428

Double (F64)

r

Stator winding resistance [p.u.]  0.011

Double (F64)

Xmd

Feed cross impedance [p.u.]  0.011

Double (F64)

rf

Feed winding resistance [p.u.]  0.011

Double (F64)

rm

Mains line resistance [p.u.]  0.011

Double (F64)

xm

Mains line reactance [p.u.]  0.011

Double (F64)

Output

if

Feed current [p.u.]

Double (F64)

u1

1st phase actual voltage [p.u.]

Double (F64)

u

RMS (phase-to-N) voltage [p.u.]

Double (F64)

i

RMS (phase) current [p.u.]

Double (F64)

p

Active power [p.u.]

Double (F64)

q

Reactive power [p.u.]

Double (F64)

freq

Frequency [p.u.]

Double (F64)

phir

Rotor actual angle [rad]

Double (F64)

phiu

Load/torque angle[rad]

Double (F64)

phim

Mains-genertor phase difference [rad]

Double (F64)

rpm

Rotation per minute

Double (F64)

cos

Power factor

Double (F64)

E

Error indicator

Bool

2024 © REX Controls s.r.o., www.rexygen.com