SELU – Controller selector unit
Block SymbolLicensing group: STANDARD
Function Description
The SELU block is tailored for selecting the active controller in selector control. It
chooses one of the input signals u1, u2, u3, u4 and copies it to the output y. For
the active signal is selected by the iSW input. In the case of
the selection is based on the binary inputs SW1 and SW2 according to the following
table:
iSW | SW1 | SW2 | y | U1 | U2 | U3 | U4 |
0 | off | off | u1 | off | on | on | on |
1 | off | on | u2 | on | off | on | on |
2 | on | off | u3 | on | on | off | on |
3 | on | on | u4 | on | on | on | off |
This table also explains the meaning of the binary outputs U1, U2, U3 and U4, which are used by the inactive controllers in selector control for tracking purposes (via the SWU blocks).
This block propagates the signal quality. More information can be found in the 1.4 section.
Input
u1..u4 | Analog input of the block | Double (F64) |
iSW | Active signal selector | Long (I32) |
SW1 | Binary signal selector | Bool |
SW2 | Binary signal selector | Bool |
Parameter
BINF | Enable the binary selectors | Bool |
|
|
|
Output
y | The selected input signal | Double (F64) |
U1..U4 | Binary output signal for selector control | Bool |