PIDAT – PID controller with relay autotuner
Block SymbolLicensing group: AUTOTUNING
Function Description
The PIDAT block has the same control function as the PIDU block. Additionally it
is equipped with the relay autotuning function.
In order to perform the autotuning experiment, it is necessary to drive the system to approximately steady state (at a suitable working point), choose the type of controller to be autotuned (PI or PID) and activate the TUNE input by setting it to on. The controlled process is regulated by special adaptive relay controller in the experiment which follows. One point of frequency response is estimated from the data measured during the experiment. Based on this information the controller parameters are computed. The amplitude of the relay controller (the level of system excitation) and its hysteresis is defined by the amp and hys parameters. In case of hys=0 the hysteresis is determined automatically according to the measurement noise properties on the controlled variable signal. The signal TBSY is set to on during the tuning experiment. While the tuning experiment is running, the ite output shows the estimated time to finish in seconds.
A successful experiment is indicated by and the controller parameters can be found on the outputs pk, pti, ptd, pnd and pb. The c weighting factor is assumed (and recommended) c=0. A failure during the experiment causes and the output ite provides further information about the problem. It is recommended to increase the amplitude amp in the case of error. The controller is equipped with a built-in function which decreases the amplitude when the deviation of output from the initial steady state exceeds the maxdev limit. The tuning experiment can be prematurely terminated by activating the TBRK input.
For the gain setting, a value of disables the controller. Negative values are not allowed (use the RACT parameter for negative effect instead). Setting the integral time constant to disables the integral component of the controller (same effect as disabling it with the irtype parameter). For , the derivative component of the controller is disabled. Static gain of the process k0 must be provided in case of .
It is recommended not to change the parameters n1, mm, ntime, rerrap and aerrph.
This block propagates the signal quality. More information can be found in the 1.4 section.
Input
dv | Feedforward control variable | Double (F64) |
sp | Setpoint variable | Double (F64) |
pv | Process variable | Double (F64) |
tv | Tracking variable | Double (F64) |
hv | Manual value | Double (F64) |
MAN | Manual or automatic mode | Bool |
|
|
|
TUNE | Start the tuning experiment | Bool |
TBRK | Stop the tuning experiment | Bool |
Parameter
irtype | Controller type (control law) 6 | Long (I32) |
|
|
|
RACT | Reverse action flag | Bool |
|
|
|
k | Controller gain 0.0 1.0 | Double (F64) |
ti | Integral time constant 0.0 4.0 | Double (F64) |
td | Derivative time constant 0.0 1.0 | Double (F64) |
nd | Derivative filtering parameter 0.0 10.0 | Double (F64) |
b | Setpoint weighting - proportional part 0.0 1.0 | Double (F64) |
c | Setpoint weighting - derivative part 0.0 | Double (F64) |
tt | Tracking time constant 0.0 1.0 | Double (F64) |
hilim | Upper limit of the controller output 1.0 | Double (F64) |
lolim | Lower limit of the controller output -1.0 | Double (F64) |
iainf | Type of apriori information 1 | Long (I32) |
|
|
|
k0 | Static gain 1.0 | Double (F64) |
n1 | Maximum number of half-periods - freq. response point 20 | Long (I32) |
mm | Maximum number of half-periods - averaging 4 | Long (I32) |
amp | Relay controller amplitude 0.1 | Double (F64) |
uhys | Relay controller hysteresis | Double (F64) |
ntime | Length of noise estimation period [s] 5.0 | Double (F64) |
rerrap | Termination value - amplitude relative error 0.1 | Double (F64) |
aerrph | Termination value - phase absolute error 10.0 | Double (F64) |
maxdev | Maximal admissible deviation error 1.0 | Double (F64) |
Output
mv | Manipulated variable (controller output) | Double (F64) |
de | Deviation error | Double (F64) |
SAT | Saturation flag | Bool |
|
|
|
TBSY | Tuner busy flag | Bool |
TE | Tuning error | Bool |
|
|
|
ite | Error code | Long (I32) |
|
|
|
pk | Proposed controller gain | Double (F64) |
pti | Proposed integral time constant | Double (F64) |
ptd | Proposed derivative time constant | Double (F64) |
pnd | Proposed derivative component filtering | Double (F64) |
pb | Proposed weighting factor - proportional component | Double (F64) |
[Previous] [Back to top] [Up] [Next]
2024 © REX Controls s.r.o., www.rexygen.com