MVD – Motorized valve drive

Block SymbolLicensing group: STANDARD
Qt SVG Document Exported by REXYGEN Studio UP DN y HS LS MVD

Function Description
The MVD block simulates a servo valve. The UP (DN) input is a binary command for opening (closing) the valve at a constant speed 1tv, where tv is a parameter of the block. The opening (closing) continues for UP = on (DN = on) until the full open y = hilim (full closed y = lolim) position is reached. The full open (full closed) position is signalized by the end switch HS (LS). The initial position at start-up is y = y0. If UP = DN = on or UP = DN = off, then the position of the valve remains unchanged (neither opening nor closing).

This block propagates the signal quality. More information can be found in the 1.4 section.

Input

UP

Open

Bool

DN

Close

Bool

Parameter

y0

Initial valve position

Double (F64)

tv

Transition time [s]  10.0

Double (F64)

hilim

Upper limit position (open)  1.0

Double (F64)

lolim

Lower limit position (closed)

Double (F64)

Output

y

Valve position

Double (F64)

HS

Upper end switch

Bool

LS

Lower end switch

Bool