0122-25 Modbus TCP Slave

Example Projects > 0122 UniPi 1.1 > 0122-25 Modbus TCP Slave

UniPi as Modbus TCP slave

This folder contains the source files for the demonstration project on using REXYGEN on the Raspberry Pi minicomputer with the UniPi extension board.

In this example the UniPi is used as a Modbus TCP slave to allow integration in complex or hierarchical control systems.

Prerequisites

  • REXYGEN Runtime Core, RPiDrv and MbDrv modules must be installed and running on the Raspberry Pi.

Running the example

  • The *exec.mdl file is the project main file.
  • Open it with REXYGEN Studio, compile and download it to the target device.

Modbus registers

Modbus holding registers are used for data exchange. Use the Read Holding Registers command (FC=03) for reading the status of UniPi inputs and the Preset Multiple Registers command (FC=16) to manipulate the outputs.

UniPi input signals

Register No. Meaning Data range
0 Digital inputs (LSB=I01) 0..4095
1 Analog input 1 (0..10V, 16-bit) 0..65535
2 Analog input 2 (0..10V, 16-bit) 0..65535

UniPi output signals

Register No. Meaning Data range
2048 UniPi relays (LSB=relay 1) 0..255
2049 Analog output (PWM on pin 18) 0..1023

Adding signals and changing Modbus register mapping

Go to Modbus TCP Slave driver (MTS block) configuration and press "Configure" for Modbus registers configuration. Make sure to read the Modbus driver documentation (see below).

Documentation

Additional information

  • More info about the UniPi board can be found at unipi.technology.
  • Raspberry Pi is a trademark of the Raspberry Pi Foundation.
  • Visit the REXYGEN webpage for more information about the example projects and developing advanced automation and control solutions using REXYGEN.

Links